The voltage generated by thermocouples is very small. They are in the order of milivolts. In the application of thermocouples to measure temperature, it is often required to convert the milivolts signals of thermocouples to temperature values. To aid this conversion, several milivolts voltages for the different types of thermocouples are tabulated against known standard temperatures. With these thermocouple reference tables, it is then easy to determine any given temperature for known milivolts values.
Thermocouple reference tables are based on a reference junction of 0 degree C. If the reference junction is not at 0 degree C, then a correction factor must be applied.
The steps involved are:
- Select the correct reference table for the thermocouple type in use. e.g. J,S,T etc
- Locate the milivolt reading in the body of the table, and read from the margins the temperature value.
a straight line approximation (or interpolation) can be made between two values.
From the little sketch above, suppose we are given the milivolts reading of a particular type of thermocouple to be VH and VL and the corresponding temperatures are TH and TL , the temperature TM corresponding to the measured voltage, VM is given by:
(VM - VL)/(VH - VL) = (TM – TL)/(TH - TL)
This simplifies to:
TM = TL + [(VM – VL)/(VH – VL)](TH – TL)
Where:
VM is the measured voltage
VH is the higher voltage read from the table
VL is the lower voltage read from the table
TM is the calculated temperature
TH is the higher temperature read from the table (corresponding to VH)
TL is the lower temperature read from the table (corresponding to VL)
The values of VH, VL, TH and TL are read from the thermocouple reference tables. Interpolation is then done using the formula above to determine the more precise temperature.
To calculate milivolts values, we use the thermoelectric voltage in milivolts for type J thermocouple reference table shown below:
A voltage of 14.82mV is measured with a type J thermocouple with a 0 degree C reference temperature. Find the temperature of the sensing junction.
Solution
From the reference table for J-type thermocouples above, it is found that VM = 14.82mV is between VL = 14.67mV and VH = 14.94mV(the red box and red arrows) These voltages have corresponding temperatures of TL = 2700C and TH = 2750C.
Using our interpolation formula, we determine the temperature to be:
TM = TL + [(VM – VL)/(VH – VL)](TH – TL)
TM = 270 + [(14.82 – 14.67)/(14.94 – 14.67)](275 – 270) = 272.80C
- Select the correct reference table for the thermocouple type in use, i.e. J,S,T etc.
- Locate the milivolt reading for the reference junction in the body of the table, and read from the margins the temperature value.
- Add this milivolt reading to that measured by the instrument.
Problem B
A voltage of 3.444 mV is measured with a type J thermocouple with a 25 degree C reference temperature. Find the temperature of the sensing junction.
Solution:
The voltage of the reference junction at 25 degree C, from the J-type reference table is 1.277mV(the blue box and blue arrow).
The measured voltage needs to be corrected such that the actual sensing voltage is the sum of the two:
1.277 + 3.444 = 4.721mV
From the J-type thermocouple reference table above, VM = 4.721mV is between VH = 4.726mV and VL = 4.672mV corresponding to TH = 900C and TL = 890C (the green box and green arrows).
TM = 89 + [(4.721 – 4.672)/(4.726 – 4.672)](90 – 89) = 89.9070C